Temperature and humidity measurement up to 200°C, with remote probe configurations and industrial analog / RS485 communication.
In heated production environments, measuring humidity involves more than selecting a sensor with a wide temperature range. Probe exposure, transmitter placement, process pressure and signal integration all affect whether a measurement system is suitable for the installation.
The HENGKO HG808-T5N4 series is designed for industrial temperature and humidity monitoring where a high-temperature sensing probe must work alongside a transmitter connected to plant automation equipment.
Installation distinction: The sensing probe may be installed in the hot process zone, while the transmitter electronics must remain within their specified ambient operating conditions. Confirm probe type, cable routing and mounting arrangement before installation.
An industrial dryer or heated chamber may expose its measurement probe to temperatures that ordinary room-condition transmitters are not designed to withstand. At the same time, the automation system still needs stable, accessible temperature and humidity data.
The sensing point and the electronics enclosure may require different installation locations because their allowable temperature conditions differ.
Oil mist, dust, condensation, chemical vapors and pressure can influence probe selection, protection and maintenance requirements.
The measurement must be delivered in a signal format that matches the PLC, DCS or data acquisition system.
The HG808-T5N4 combines temperature and humidity sensing with configurable signal output and digital data access, reducing the need to use separate instruments for basic process monitoring.
Split and pipeline-style probe arrangements allow engineers to select a mounting method suited to the sensing location and equipment structure.
Two analog channels can carry temperature and relative humidity signals, while RS485 provides digital access to additional measurement values.
Standard industrial communication supports integration with compatible controllers and supervisory systems. Register mapping and configuration should be checked against the device documentation.
The source specifications list temperature, relative humidity, dew point and PPM values through RS485. Confirm the PPM definition and applicable calculation conditions for your project.
The original design information specifies reverse-polarity, overcurrent and ESD protection features, alongside a 10–28 V DC supply range.
The following values are taken from the supplied product information. Performance at extreme temperatures and compatibility with specific process conditions must be confirmed for the selected probe assembly.
| Temperature Range | −40 to +200°C |
|---|---|
| Humidity Range | 0–100% RH; recommended below 95% RH |
| Temperature Accuracy | ±0.1°C at 20°C |
| Humidity Accuracy | ±2% RH at 20°C, 10–90% RH |
| Selectable Resolution | 0.01 or 0.1°C; 0.01 or 0.1% RH |
| Acquisition Interval | As fast as 1 second, according to original specifications |
| Power Supply | 10–28 V DC |
|---|---|
| Power Consumption | Less than 0.5 W |
| Analog Outputs | Two channels for temperature and humidity; 4–20 mA, 0–5 V or 0–10 V configuration |
| Digital Interface | RS485, Modbus RTU |
| Digital Variables | Temperature, RH, dew point and PPM |
| Baud Rates | 1200 / 2400 / 4800 / 9600 / 19200 / 115200 bps |
| Default Baud Rate | 9600 bps |
| Serial Format | 8 data bits, 1 stop bit, no parity |
| Transmitter Ambient Conditions | −20 to +60°C; 0–95% RH, non-condensing |
|---|---|
| Pressure Rating | 16 bar listed; applicability to the selected probe assembly requires confirmation |
| Probe Options Listed | 3A / 3B, 5A / 5B, 6A / 6B |
| Probe Arrangements | Split-type and pipeline-style options |
For high-temperature measurement, the probe is often the first component to specify. The sensing location, process connection, exposure conditions and installation depth determine which assembly is appropriate.
The original HG808 series information refers to a broader probe family. Not every illustrated probe should be assumed to support the T5N4 high-temperature configuration.
The transmitter offers analog and digital communication paths. The correct choice depends on the controller's input modules, required variables and the facility's existing instrumentation architecture.
Choose a compatible 4–20 mA, 0–5 V or 0–10 V output configuration when the control system uses analog input channels. The selected analog output type should match the PLC input hardware.
Use RS485 to read supported digital variables from compatible PLC, DCS or supervisory software. Match the serial parameters and register addresses to the supplied communication documentation.
The HG808-T5N4 is most relevant where the sensing point is exposed to elevated temperatures and the process requires temperature and humidity information for monitoring or control. Suitability depends on the actual probe and process conditions.
Drying systems may require humidity and temperature trends to assess changes during the drying cycle. Probe position, contamination and moisture exposure should be evaluated before installation.
Temperature and humidity measurements can support test monitoring, provided the chamber's operating profile remains within the approved sensor limits.
Humidity and temperature data may help operators observe the conditions surrounding heated curing or coating processes. Sensor exposure to solvents or process vapors must be assessed separately.
Selected duct installations may benefit from combined temperature and humidity measurement. Gas composition, pressure, particulates and condensation risk require engineering review.
A complete inquiry should describe both the measurement conditions and the required electrical interface. This helps avoid selecting a suitable sensor element with an unsuitable mounting or output configuration.
Minimum and maximum temperature, humidity range, pressure, gas composition and possible contamination.
Probe style, insertion length, connection dimensions, cable length and transmitter mounting location.
4–20 mA, voltage output or RS485; controller model, communication settings and measurement variables.
Quantity, expected delivery schedule, calibration documentation and any project-specific certificates.
No. The original specifications distinguish the high-temperature measurement range from the transmitter electronics' ambient range of −20 to +60°C. The installation must respect both limits.
The supplied accuracy value is stated at 20°C. Request the full temperature-dependent accuracy specification if your application requires a defined uncertainty at elevated temperatures.
The product information describes analog channels and an RS485 digital interface. Confirm simultaneous operation and the available output combination for the exact order code.
Do not assume compatibility from temperature rating alone. Condensation, gas chemistry, process pressure and protective materials must be reviewed for the specific installation.
Analog outputs may suit existing analog input modules. RS485 Modbus RTU can provide digital access to multiple measurement values when supported by the controller.
Provide the operating temperature and humidity range, process medium, pressure, probe dimensions, installation method, output requirements and quantity.
Tell us about your process temperature, humidity range, probe installation, output interface and required quantity. HENGKO can help review the HG808-T5N4 configuration against your application requirements.