High-Temp 200°C Humidity Transmitter for Industrial Ovens & Drying Systems by HENGKO HG808-T5N4

HG808-T5N4 | HIGH-TEMPERATURE PROCESS INSTRUMENTATION

High-Temperature Humidity Transmitter for Industrial Process Monitoring

Temperature and humidity measurement up to 200°C, with remote probe configurations and industrial analog / RS485 communication.

In heated production environments, measuring humidity involves more than selecting a sensor with a wide temperature range. Probe exposure, transmitter placement, process pressure and signal integration all affect whether a measurement system is suitable for the installation.

The HENGKO HG808-T5N4 series is designed for industrial temperature and humidity monitoring where a high-temperature sensing probe must work alongside a transmitter connected to plant automation equipment.

200°C
Specified upper measurement limit
RS485
Modbus RTU communication
Dual Analog 
Temperature and RH analog outputs
10–28 V
DC power supply

Installation distinction: The sensing probe may be installed in the hot process zone, while the transmitter electronics must remain within their specified ambient operating conditions. Confirm probe type, cable routing and mounting arrangement before installation.

01 / MEASUREMENT CHALLENGE

Why High-Temperature Humidity Measurement Requires a Different Approach

An industrial dryer or heated chamber may expose its measurement probe to temperatures that ordinary room-condition transmitters are not designed to withstand. At the same time, the automation system still needs stable, accessible temperature and humidity data.

Three Engineering Considerations

01 — THERMAL SEPARATION

The sensing point and the electronics enclosure may require different installation locations because their allowable temperature conditions differ.

02 — PROCESS EXPOSURE

Oil mist, dust, condensation, chemical vapors and pressure can influence probe selection, protection and maintenance requirements.

03 — CONTROL SYSTEM INTEGRATION

The measurement must be delivered in a signal format that matches the PLC, DCS or data acquisition system.

02 / FUNCTIONAL DESIGN

Designed Around the Needs of Industrial Control Systems

The HG808-T5N4 combines temperature and humidity sensing with configurable signal output and digital data access, reducing the need to use separate instruments for basic process monitoring.

Remote and Pipeline Probe Options

Split and pipeline-style probe arrangements allow engineers to select a mounting method suited to the sensing location and equipment structure.

Analog and Digital Measurement Access

Two analog channels can carry temperature and relative humidity signals, while RS485 provides digital access to additional measurement values.

Modbus RTU Communication

Standard industrial communication supports integration with compatible controllers and supervisory systems. Register mapping and configuration should be checked against the device documentation.

Digital Measurement Variables

The source specifications list temperature, relative humidity, dew point and PPM values through RS485. Confirm the PPM definition and applicable calculation conditions for your project.

Electrical Protection

The original design information specifies reverse-polarity, overcurrent and ESD protection features, alongside a 10–28 V DC supply range.

03 / TECHNICAL DATA

HG808-T5N4 Technical Specifications

The following values are taken from the supplied product information. Performance at extreme temperatures and compatibility with specific process conditions must be confirmed for the selected probe assembly.

Measurement Performance
Temperature Range −40 to +200°C
Humidity Range 0–100% RH; recommended below 95% RH
Temperature Accuracy ±0.1°C at 20°C
Humidity Accuracy ±2% RH at 20°C, 10–90% RH
Selectable Resolution 0.01 or 0.1°C; 0.01 or 0.1% RH
Acquisition Interval As fast as 1 second, according to original specifications
Electrical and Communication
Power Supply 10–28 V DC
Power Consumption Less than 0.5 W
Analog Outputs Two channels for temperature and humidity; 4–20 mA, 0–5 V or 0–10 V configuration
Digital Interface RS485, Modbus RTU
Digital Variables Temperature, RH, dew point and PPM
Baud Rates 1200 / 2400 / 4800 / 9600 / 19200 / 115200 bps
Default Baud Rate 9600 bps
Serial Format 8 data bits, 1 stop bit, no parity
Installation and Probe Configuration
Transmitter Ambient Conditions −20 to +60°C; 0–95% RH, non-condensing
Pressure Rating 16 bar listed; applicability to the selected probe assembly requires confirmation
Probe Options Listed 3A / 3B, 5A / 5B, 6A / 6B
Probe Arrangements Split-type and pipeline-style options
Specification clarification: The temperature and humidity accuracy values above are specified at 20°C. They should not be interpreted as guaranteed accuracy across the full measurement range. Confirm the probe's maximum continuous exposure temperature, pressure rating, humidity operating envelope and calibration requirements before purchase.
04 / PROBE SELECTION

Select the Probe Before Finalizing the Transmitter

For high-temperature measurement, the probe is often the first component to specify. The sensing location, process connection, exposure conditions and installation depth determine which assembly is appropriate.

Probe Selection Checklist

●Required process temperature and duration of exposure
●Probe insertion depth and mounting location
●Process pressure and connection type
●Presence of dust, oil mist or chemical vapors
●Required cable length and routing conditions
●Maintenance and calibration access

The original HG808 series information refers to a broader probe family. Not every illustrated probe should be assumed to support the T5N4 high-temperature configuration.

05 / AUTOMATION INTEGRATION

Connecting HG808-T5N4 to a PLC or Monitoring System

The transmitter offers analog and digital communication paths. The correct choice depends on the controller's input modules, required variables and the facility's existing instrumentation architecture.

OPTION A

Analog Process Signals

Choose a compatible 4–20 mA, 0–5 V or 0–10 V output configuration when the control system uses analog input channels. The selected analog output type should match the PLC input hardware.

OPTION B

RS485 Modbus RTU

Use RS485 to read supported digital variables from compatible PLC, DCS or supervisory software. Match the serial parameters and register addresses to the supplied communication documentation.

Wiring precaution: The image is a reference from the HG808 product family. Verify terminal assignments, wire colors, power polarity and output configuration against the exact unit supplied before energizing the circuit.
06 / INDUSTRIAL USE CASES

Where High-Temperature Humidity Data Supports Process Control

The HG808-T5N4 is most relevant where the sensing point is exposed to elevated temperatures and the process requires temperature and humidity information for monitoring or control. Suitability depends on the actual probe and process conditions.

APPLICATION 01

Industrial Drying Equipment

Drying systems may require humidity and temperature trends to assess changes during the drying cycle. Probe position, contamination and moisture exposure should be evaluated before installation.

APPLICATION 02

Heated Environmental Test Chambers

Temperature and humidity measurements can support test monitoring, provided the chamber's operating profile remains within the approved sensor limits.

APPLICATION 03

Coating and Curing Processes

Humidity and temperature data may help operators observe the conditions surrounding heated curing or coating processes. Sensor exposure to solvents or process vapors must be assessed separately.

APPLICATION 04

Industrial Process Ducts

Selected duct installations may benefit from combined temperature and humidity measurement. Gas composition, pressure, particulates and condensation risk require engineering review.

07 / ORDER CONFIGURATION

Specify the Transmitter for Your Installation

A complete inquiry should describe both the measurement conditions and the required electrical interface. This helps avoid selecting a suitable sensor element with an unsuitable mounting or output configuration.

Process conditions

Minimum and maximum temperature, humidity range, pressure, gas composition and possible contamination.

Mechanical installation

Probe style, insertion length, connection dimensions, cable length and transmitter mounting location.

Control system requirements

4–20 mA, voltage output or RS485; controller model, communication settings and measurement variables.

Purchasing requirements

Quantity, expected delivery schedule, calibration documentation and any project-specific certificates.

08 / TECHNICAL QUESTIONS

HG808-T5N4 Engineering FAQ

Can the entire transmitter be installed at 200°C?

No. The original specifications distinguish the high-temperature measurement range from the transmitter electronics' ambient range of −20 to +60°C. The installation must respect both limits.

Is ±0.1°C accuracy available throughout the full temperature range?

The supplied accuracy value is stated at 20°C. Request the full temperature-dependent accuracy specification if your application requires a defined uncertainty at elevated temperatures.

Can analog outputs and RS485 be used together?

The product information describes analog channels and an RS485 digital interface. Confirm simultaneous operation and the available output combination for the exact order code.

Is the transmitter suitable for steam or chemically aggressive gases?

Do not assume compatibility from temperature rating alone. Condensation, gas chemistry, process pressure and protective materials must be reviewed for the specific installation.

Which output is preferable for PLC integration?

Analog outputs may suit existing analog input modules. RS485 Modbus RTU can provide digital access to multiple measurement values when supported by the controller.

What should be included in a quotation request?

Provide the operating temperature and humidity range, process medium, pressure, probe dimensions, installation method, output requirements and quantity.